CPSC, Greenheck Fan Corp. Announce Recall of Ventilation Units
Hazard
LUX 3/8-inch spinlock bolts supplied with these units may not have been properly heat treated, which can result in the bolts breaking. Bolt failure during lifting for rooftop installation or after installation could cause the unit or components to fall and injure bystanders.
Be the first to hear about future recalls.
Add the things you own to a watchlist. We’ll alert you the moment one matches.
Get started, freeDescription
Affected units are Sidewall, Rooftop and Centrifugal Inline ventilation units built between August 11, 2004 and April 29, 2005, containing 16-thread-per-inch 3/8-inch by ¾-inch spinlock bolts with LUX head markings. Affected model numbers are RBU, RBUMO, RDU, RB/R, SB/S, and BSU 360-420 with serial numbers 04HXXXXX through 05DXXXXX. The model and serial numbers are found on metal identification plate on the units.
Product details
- Product
- Greenheck Sidewall, Rooftop and Centrifugal Inline Ventilation Units
- Type
- Ventilators
- Manufacturer
- Not specified
- Model numbers
- 04HXXXXX, 05DXXXXX
- UPCs
- —
- Sold at
- Independent sales representatives and original equipment manufacturers, from August 2004 through July 2005.
- Made in
- Taiwan
What you should do
LUX spinlock bolts in affected units will be replaced at no cost to the end user.