CPSC, Greenheck Fan Corp. Announce Recall of Ventilation Units

Hazard

LUX 3/8-inch spinlock bolts supplied with these units may not have been properly heat treated, which can result in the bolts breaking. Bolt failure during lifting for rooftop installation or after installation could cause the unit or components to fall and injure bystanders.

Be the first to hear about future recalls.

Add the things you own to a watchlist. We’ll alert you the moment one matches.

Get started, free

Description

Affected units are Sidewall, Rooftop and Centrifugal Inline ventilation units built between August 11, 2004 and April 29, 2005, containing 16-thread-per-inch 3/8-inch by ¾-inch spinlock bolts with LUX head markings. Affected model numbers are RBU, RBUMO, RDU, RB/R, SB/S, and BSU 360-420 with serial numbers 04HXXXXX through 05DXXXXX. The model and serial numbers are found on metal identification plate on the units.

Product details

Product
Greenheck Sidewall, Rooftop and Centrifugal Inline Ventilation Units
Type
Ventilators
Manufacturer
Not specified
Model numbers
04HXXXXX, 05DXXXXX
UPCs
Sold at
Independent sales representatives and original equipment manufacturers, from August 2004 through July 2005.
Made in
Taiwan

What you should do

LUX spinlock bolts in affected units will be replaced at no cost to the end user.