CPSCRecalled Mar 31, 2016 · #16134
Gamewell-FCI Recalls Fire Alarm Panels Due to Failure to Alert of a Fire, Smoke or CO
Hazard
When configured in a certain way, the panels can become non-responsive and connected detectors in the area can fail to detect and respond to an alarm.
Be the first to hear about future recalls.
Add the things you own to a watchlist. We’ll alert you the moment one matches.
Get started, freeDescription
This recall is for the ILI-MB-E3 and ILI-S-E3 Gamewell-FCI fire alarm panels in commercial buildings. This issue is limited to a specific configuration of Signaling Line Circuit (SLC) devices. To occur, the SLC must include at least two of the following detectors in any combination: Acclimate, 4-Warn, Photo/CO and iFAAST. The issue would occur only if the detectors are addressed within the same FlashScan polling group. Detectors installed in a different combination are not affected.
Product details
- Product
- Gamewell-FCI fire alarm panels (ILI-MB-E3 and ILI-S-E3)
- Type
- Fire or Smoke Alarms
- Manufacturer
- Not specified
- Model numbers
- —
- UPCs
- —
- Sold at
- Authorized distributors from May 2015 through August 2015 for about $800.
- Made in
- United States
What you should do
Consumers should immediately contact the distributor to obtain the free repair, a firmware upgrade.